Industrial gas detector series Parameters Remarks
fixed gas detector,industrial gas detector

Gas Transmitter: Type:AIG-1

Detect Gas: Combustible gas, Flammable gas
1. Enivronmental parameter:
temperature: -20℃~+50℃
RH: ≤90% (Non-condensing)
2. Technical parameter:
Working voltage: 16~30VDC
Working current: 120mA
Output signal: 4~20mA standard signal with 3-wire system output, RS485 outputs;
3. Sensor: Catalytic Sensor
4. Response time: T9 less than 30 seconds
5. Effect range: 0-100%LEL
6. Installation parameter:Wall mounting type
Transmission cable: three-core shielded cable
7. Section: 3×1.5sqmm, outer diameter: ¢10mm
Transmission range: ≤1000m
8. Class of explosive-proof:
Exd IICT6Gb (explosive insulation); ExiaIICT4 (Intrinsically Safe application)
9. Grade of Protection:IP65
10. Connector: G1/2 (Insidethread)
11.Size:183*143*92mm

This detector is specially for industrial or commercial areas, kitchen in hotel, plants, etc.

Should work with the gas control panel AIP-P1

fixed gas detector,industrial gas detector

Gas Transmitter: Type:AIG-2

Detect Gas: Combustible gas, Flammable gas

1.Class of explosive-proof:
Exd IICT6/T5/T4
2.Detection Range: 0-100%LEL
3.Detection Tolerance:-3%<x<+3%(F.S)
4.Response Time:<25s
5.Voltage:DC24V
6.Consumption:1.8W
7.Ambient Temperature:-20-50Centi degree
8.Connection Size: G1/2, M20*1.5
9.Output:Addressable or conventional type optional
10. Sensor:Catalytic Sensor

Kits:AIG-2 detector+ AIG-P2 control panel

fixed gas detector,industrial gas detector

Gas Transmitter: Type:AIG-3

Detect Gas: Combustible gas, Flammable gas
1. Enivronmental parameter:
temperature: -20℃~+50℃
RH: ≤90% (Non-condensing)
2. Technical parameter:
Power consumption:<3W;
Output signal: 4~20mA standard signal with 3-wire system output, RS485 outputs;NO/NC signal to DCS, PLC optional
3. Sensor: Catalytic Sensor
4.Display method: LED display to indicate index of density of the gas
5. Effect range: 0-100%LEL
6.Grade of Protection:IP65
7.Transmission range: ≤1000m
8. Class of explosive-proof:
Exd IICT6Gb (explosive insulation);
9. Grade of Protection:IP65
10.Debug method: IR remote

This detector is specially for industrial or commercial areas, kitchen in hotel, plants, etc.

Should work with the gas control panel AIG-P1

fixed gas detector,industrial gas detector control panel

Type:AIG-P1

Gas detector control panel

Detect Gas: LPG, Natural gas, Combustible gas, Flammable gas

1.Range type: %LEL, %VOL, PPM
2.Alarm level: 2 levels alarms, set by user
3.Preset level:(EX)low alarm:25%LEL; High alarm: 50%LEL;
4.Display method: LED display indicates the value of density , status of alarm or fault.
5.Input: 4-20ma input, RS485 addressable input
6.Installation type:Wall mounted
7. Communications:
(1)Conventional type: 2,4,8 Channels, 4-20mA input;
(2)Addressable type:12, 16, 24, 32 protection zones, RS485 input
8.Working environment:-20℃~+50℃ RH: ≤90% (Non-condensing)
9.Working voltage: AC220 50Hz
10.Power consumption: Control Panel: 6W max, Detector: 1W max;
10.Execute criterion:GB16808-1997

AIG-1, AIG-2 compatible

Type:AIG-P2

Gas detector control panel

Detect Gas: LPG, Natural gas, Combustible gas, Flammable gas

1.Detection Range: 0-100%LEL
2.Alarm level: 2 levels alarms, set by user
3.Preset level:(EX)low alarm:25%LEL; High alarm: 50%LEL;
4.Display method: LCD display indicates the value of density , status of alarm or fault.
5.Input: NO/NC, RS485
6.Installation type:Wall mounted
7. Communications:
(1)Conventional type: 4-20mA input;
(2)Addressable type: RS485 input
8.Working environment:-20℃~+50℃ RH: ≤90% (Non-condensing)
9.Working voltage: AC220 50Hz
10.Power backup: External power backup 24V14Ah;
10.Protection zones:32, 64, 127, 256 points

AIG-3 compatible
fixed gas detector,industrial gas detector control panel

Type:AIG-P3

Gas detector control panel

Detect Gas: LPG, Natural gas, Combustible gas, Flammable gas

1.Alarm setting: L-1 alarm point: program fixed
L-2 alarm point:program fixed
2.Alarm type: Sound & Flash
3.Alarm volume: > 120 db
4.Alarm output: electrical independent contact , capacity: AC220v 5A
5.Ambient temp: -10℃ ~ 50℃
6.RH : < 90% non condensing
7.Proof level: IP44
8.Power : AC220V,50HZ <4W
9.Transmission distance: 1000m < 2sqmm copper wire
10.Size::480(L)*250(W)×130(H)mm    Weight:4.0kg